| tert-Butyl mercaptan & Dimethyl Sulfide | (CH3)3CSH | NO.77 |
|
|
||

| Performance | (Simultaneous detector tube) |
| Detector Tube | TBM Tube | DMS Tube | |
|
Measuring Range |
1 to 15 mg/m3 |
1 to 15 mg/m3 |
|
|
Number of Pump Stroke |
1 |
1 |
|
|
Correction Factor |
1 |
1 |
|
|
Sampling Time |
3 minutes per pump stroke |
||
|
Detecting Limit |
0.2 mg/m3 (n=1) |
||
|
Color Change |
Yellow |
Pink |
|
|
Reaction Formula |
tert-Butyl Mercaptan Tube Dimethyl Sulfide Tube |
||
| Coefficient of Variation | 10% (for 1 to 5 mg/m3), 5% (for 5 to 15 mg/m3) | ||
| Shelf Life | 2 Years | ||
| Corrections for temperature & humidity |
Temperature correction is necessary | ||
| Store the tubes in the refrigerator to keep at 10oC (50oF) or below. | |||
| Possible coexisting substances and their interferences | (NOTE) |
|
Substance |
Concentration |
Interference |
Change color by itself |
|
Hydrogen sulfide |
- |
Plus error |
Discolor to Pink |
|
Mercaptans |
- |
Plus error |
Discolor to Pink |
|
Substance |
Concentration |
Interference |
Change color by itself |
|
Olefins |
- |
Plus error |
Discolor to Pale yellow |
|
Tetrahydrothiophene |
- |
Plus error |
Discolor to Pale yellow |
| Calibration gas generation | TBM Tube:Diffusion tube method DMS Tube:Permeation tube method |
|
| TLV-TWA | TLV-STEL | Explosive range |
| - | - | - |
|
|
| Copyright(c) 2001 GASTEC CORPORATION. All rights reserved. |