| Hydrogen sulfide | H2S | NO.4H | |
|
|
|||

| Performance |
|
Measuring Range |
10 to 100 ppm |
100 to 2000 ppm |
2000 to 4000 ppm |
|
Number of Pump Strokes |
2 to 10 |
1 |
1/2 |
|
Correction Factor |
1/2 to 1/10 |
1 |
2 |
|
Sampling Time |
30 seconds per pump stroke |
||
|
Detecting Limit |
2 ppm (n=10) |
||
|
Color Change |
White |
||
|
Reaction Principle |
Hydrogen sulfide reacts with lead acetate to |
||
| Coefficient of Variation | 5% (for 100 to 2000 ppm) | ||
| Shelf Life | 3 Years | ||
| Corrections for temperature & humidity |
Unnecessary | ||
| Store the tubes at cool and dark place. | |||
| Possible coexisting substances and their interferences | (NOTE) |
|
Substance |
Concentration |
Interference |
Change color by itself |
|
Ammonia |
- |
No effect |
No discoloration |
|
Carbon monoxide, |
- |
No effect |
No discoloration |
|
Sulfur dioxide |
1 time |
Plus error |
No discoloration |
|
Mercaptans |
- |
No effect |
No discoloration |
|
Organic substance |
- |
No effect |
No discoloration |
| Calibration gas generation | Permeation tube method | |
| TLV-TWA | TLV-STEL | Explosive range |
| 10ppm | 15ppm | 4.0 to 44% |
|
|
| Copyright(c) 2001 GASTEC CORPORATION. All rights reserved. |